Trip Flag

indications. It is suitable for the trip display of CT powered protection devices with electrical impulse output. In addition to the display, output relays are activated. Each output has 2 changeover contacts. The output contacts and the display are latching and are reset manually via a rotary knob.

Category:

Specifications:

Indication
2 trip displays (black / red)

Relay contacts4
Remote contact
Contact capacity: 230 V AC/1 A/62.5 VA max.
220 V DC/1 A/60 W max.
External auxiliary supplyElectrical impulse, 24 V DC ≥0.01 Ws
Housing
Polycarbonate, IP40

Temperature range -30 to +70 °C